Water-heating boiler gas-fired RSH-200
  • Heat power: 200 kW

    Water temperature regulation range: +50..+115°C

    Max. heating agent pressure: 0,6 (optionally 1,0) MPa

    Fuel: gas

    Max.fuel consumption: (natural gas) 24,0 m³/hour

    Boiler water volume: 36,6 L

    Weight, no more: 1150 kg

    ORDER THE EQUIPMENT'S IN EXISTENCE

Gas-fired water-tube boiler for external installation, fully assembled inside of metal insulated block. The boiler equipped with atmospheric burner. The heat exchanger is made of finned tubes with high heat transfer surface.

Type of fuel:

  • Natural gas GOST 5542-87,
  • Liquefied petroleum gas LPG (propane-butane)

The complete set of the boiler for external installation includes:

  • boiler RSA series;
  • instruments (pressure control, water temperature control, gas low pressure control);
  • pipelines and valves.

Additional equipment for water-heating boiler is available optionally:

  • circulation pump, mesh filter (Y-strainer), safety valves;
  • methane gas contamination alarm;
  • thermal shut-off valve;
  • emergency signal transmission system via radio or to the owner's cell phone.
Heat power
       -natural gas kW 200
       -LPG kW 180
Instruments HONEYWELL VR432
Fuel type газ
ДInlet gas pressure before burner (natural gas):
       -minimum kPa 1
       -nominal kPa 2
       -maximum kPa
4
Inlet gas pressure before burner (LPG):
       -nominal kPa 3,7
Gas consumption max. (natural gas) m³/hour 24,0
Gas consumption min. (natural gas) m³/hour 12,0
Gas consumption nom. (LPG) m³/hour 23,0
Heating agent type  
drinking water GOST2874-73
Pressure loss in outlet pipeline after boiler
       -minimum
Pa 10
       -maximum Pa 40
Pump specification
       -model   NM-32/12DE,"Calpeda"
       -capacity m³/hour 10,0
       -head m WC 18,0
       -power kW 0,75
       -voltage V
220
Water working pressure MPa 0,6 (optionally 1,0)
Water temperature regulation range С° +50..+115
Min. water consumption throughout the boiler (according to «boiling prevention» clause) m³/hour 9,2
Boiler water volume L 20,136,6
Max. allowable flow resistance of heating system m WC 14
Boiler flow resistance m WC 3,0
Connection thread:
       -inlet gas connection mm DN 32
       -nozzle for heating system connection mm DN 52
Smokestack size mm DN 300
Class of fire risk ГН
Ambient class У1
Ambient temperature С° -45..+40
Efficiency, no less % 93
Weight, no more kg 1150

Item
Equipment title
   
1
Gas pipeline
mm DN32
2
Smokestack
mm DN350 
3
Air inflowing gap
cm 2х200
4
Inlet pipeline
mm DN50
5
Outlet pipeline
mm DN50
6
Gas vent
mm DN25
7
Boiler\’s drainage
mm DN15
8
Safety relief valve
mm DN15
B

mm 1500
L

mm 2220
H

mm 1800
B1

mm 750
B2

mm 210
H1

mm 1680
H2

mm 1350
H3

mm 180
L1

mm 1190
L2

mm 290
L3

mm 480
L4

mm 865
L5

mm 690
L6

mm 570